Cal. Code Regs. tit. 25, § 4517.8
(b) Minimum size of inlet connections shall be determined by the total number of fixtures to be connected to the tank.
Toilet connections shall be 3-inch minimum pipe size and shall extend vertically. The inlet fitting shall not extend downward into the tank more than 1 ½ inches (38 mm). The toilet connection shall be designed to receive or conform to an approved shape closet flange of standard dimensions or other approved fitting.
(c) Body waste holding tank drain opening shall be a minimum 3-inch pipe size. Liquid waste holding tank drain opening shall be a minimum 1 ½ inch pipe size. Drain openings shall be located at the lowest point in the tank.
A listed fullway valve shall be directly connected to the tank or installed in the drain pipe of the tank within 36 inches (915 mm) of the drain outlet.
(d) The tank shall be vented at the highest point in the top of the tank by one of the following methods:
Waste holding tanks installed in plumbing systems shall comply with the following:
Note: Authority cited: Section 18020, Health and Safety Code. Reference: Section 18055, Health and Safety Code.