- (a) Connections of aluminum conductors shall be made only inside boxes or equipment enclosures which are designed and installed to prevent the entry or accumulation of moisture within the enclosure.
- (b) Only connectors which are listed for use with aluminum conductors shall be used to connect aluminum conductors. If more than one conductor is connected to a connector, the connector shall be provided with a terminal fitting for each conductor.
- (c) Prior to inserting an aluminum conductor into the connector, the conductor from which the insulation has been removed shall be wire-brushed and sealed with an approved oxide-inhibiting joint compound.
Note: Authority cited: Section 18865, Health and Safety Code. Reference: Section 18873.3, Health and Safety Code.
History
1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).