- (a) Overfill prevention equipment must be tested upon installation and at least once every 36 months by a service technician meeting the requirements of section 2633.
- (b) Overfill prevention equipment testing must be conducted using a test procedure that demonstrates that the overfill prevention equipment will activate when the tank is filled to no more than the liquid level specified in section 2640(f). These tests must be performed in accordance with manufacturer's guidelines, an applicable method specified in an industry code or engineering standard, or if approved by the Unified Program Agency, a test method developed by a state registered professional engineer.
- (c) The results of the overfill prevention equipment test must be recorded on the “Overfill Prevention Equipment Testing Report Form” located in appendix 7.
Note: Authority cited: Sections 25299.3 and 25299.7, Health and Safety Code. Reference: Sections 25284.1 and 25284.2, Health and Safety Code; and 40 CFR Sections 280.30 and 280.35.
History
1. New section filed 4-5-94; operative 5-5-94 (Register 94, No. 14).
2. Amendment of section heading, section and Note filed 8-27-2018; operative 10-1-2018 (Register 2018, No. 35).
3. Repealer and new section heading and section filed 10-28-2025; operative 1-1-2026 (Register 2025, No. 44).