Cal. Code Regs. tit. 22, § 66265.192
(a) Owners or operators of new tank systems or components shall ensure that the foundation, structural support, seams, connections, and pressure controls (if applicable) are adequately designed and that the tank system has sufficient structural strength, compatibility with the waste(s) to be transferred, stored or treated, and corrosion protection so that it will not collapse, rupture, or fail. The owner or operator shall obtain a written assessment reviewed and certified by an independent, qualified, professional engineer, registered in California in accordance with section 66270.11(d) attesting that the system has sufficient structural integrity, is acceptable for the transferring, storing and treating of hazardous waste, and that the tanks and containment system are suitably designed to achieve the requirements of this article. This assessment shall be obtained prior to placing the tank system in service, and shall be kept on file at the facility. This assessment shall also include, at a minimum, the following information:
(3) for new tank systems or components in which the external shell of a metal tank or any external metal component of the tank system is or will be in contact with the soil or with water, a determination by a corrosion expert of:
(A) factors affecting the potential for corrosion, including but not limited to:
(B) the type and degree of external corrosion protection that are needed to ensure the integrity of the tank system during the use of the tank system or component, consisting of one or more of the following:
(5) design considerations to ensure that:
(b) The owner or operator of a new tank system shall ensure that proper handling procedures are adhered to in order to prevent damage to the system during installation. Prior to covering, enclosing, or placing a new tank system or component in use, an independent, qualified installation inspector or an independent, qualified, professional engineer, registered in California, either of whom is trained and experienced in the proper installation of tank systems, shall inspect the system or component for the presence of any of the following items:
(g) The owner or operator shall obtain and keep on file at the facility written statements by those persons required to certify the design of the tank system and supervise the installation of the tank system in accordance with the requirements of subsections (b) through (f) of this section to attest that the tank system was properly designed and installed and that repairs, pursuant to subsection (b) and (d) of this section were performed. These written statements shall also include the certification statement as required in section 66270.11(d) of this division.
(2) The provisions of subsection (h)(1) of this section apply only to:
(B) onground or aboveground tank systems containing RCRA hazardous waste generated onsite, if:
(h)(1) Notwithstanding subsections (a) through (g) of this section, design and installation of new tank systems or components used to manage hazardous waste, and which meet the criteria specified in subsection (h)(2) of this section, are not subject to the requirements of subsections (h) through (m) of this section until January 24, 1998. The assessment specified in subsection (k) of this section shall be obtained prior to placing a new tank system in service and shall be kept on file at the facility. This assessment shall be reviewed and certified by an independent, qualified, professional engineer, registered in California, in accordance with section 66270.11(d), attesting that the tank system has sufficient structural integrity and is acceptable for the transferring, storing and treating of hazardous waste. The assessment shall be valid for a maximum period of five (5) years or the remaining service life of the tank system, as stated in the engineer's assessment, whichever is less.
(j) New, onground or aboveground non-RCRA tank systems or tank systems otherwise exempt from permitting requirements pursuant to the federal act, with secondary containment, whose design and installation have been approved by a local agency or agencies, may, at the discretion of the CUPA, be exempt from the engineering assessment specified in subsection (k) of this section, provided minimum criteria specified in subsections (j)(1) through (j)(3) of this section are met. If the CUPA determines to exempt a new tank system from the assessment required pursuant to this subsection, the exemption shall be for a period of not more than three (3) years from the date the exemption was granted. The tank system owner or operator shall submit documentation of local agency approval to the applicable CUPA for review and possible acceptance in lieu of the assessment specified in subsection (k) of this section. If there is no CUPA, or the CUPA requests that the Department make a determination, the documentation shall be submitted to the Department.
(k) The tank system assessment shall include all of the following information:
(2) design standard(s), if available, according to which the tank and ancillary equipment were or will be constructed and all of the following information:
(9) prior to placing a new tank system or component in use, an independent, qualified installation inspector or an independent, qualified, professional engineer, registered in California, either of whom is trained and experienced in the proper installation of tank systems, shall inspect the system or component for the presence of any of the following items and document in writing the results of the inspection:
(l) The assessment specified in subsection (k) of this section is not required for the replacement of the following identical or functionally equivalent tank system parts or components:
(m) Replacement of identical or functionally equivalent tank system parts or components not listed in subsection (l) of this section shall be approved by the CUPA prior to replacement or changeout. If the tank system part or component is determined to be identical or functionally equivalent by the CUPA, the assessment specified in subsection (k) of this section is not required. The owner or operator shall provide the CUPA, or the Department if there is no CUPA or the CUPA requests that the Department make a determination, with the following information in writing so that a determination can be made:
Note: Authority cited: Sections 25150 and 25159, Health and Safety Code. Reference: Sections 25159 and 25159.5, Health and Safety Code; and 40 CFR Section 265.192.
1. New section filed 5-24-91; operative 7-1-91 (Register 91, No. 22).
2. New subsections (h)(1)-(h)(2)(B)2. filed 6-19-95 as an emergency; operative 6-19-95 (Register 95, No. 25). A Certificate of Compliance must be transmitted to OAL by 10-17-95 or emergency language will be repealed by operation of law on the following day.
3. New subsections (h)(1)-(h)(2)(B)2. refiled 10-16-95 as an emergency; operative 10-16-95 (Register 95, No. 42). A Certificate of Compliance must be transmitted to OAL by 2-13-96 or emergency language will be repealed by operation of law on the following day.
4. New subsections (h)(1)-(h)(1)(B)2. refiled 2-16-96 as an emergency; operative 2-16-96 (Register 96, No. 7). A Certificate of Compliance must be transmitted to OAL by 6-15-96 or emergency language will be repealed by operation of law on the following day.
5. New subsections (h)(1)-(h)(1)(B)2. refiled 6-17-96 as an emergency; operative 6-17-96 (Register 96, No. 25). A Certificate of Compliance must be transmitted to OAL by 10-15-96 or emergency language will be repealed by operation of law on the following day.
6. New subsections (h)(1)-(h)(2)(B)2. refiled 10-15-96 as an emergency; operative 10-15-96 (Register 96, No. 42). A Certificate of Compliance must be transmitted to OAL by 2-12-97 or emergency language will be repealed by operation of law on the following day.
7. Editorial correction removing duplicative subsection (g) (Register 97, No. 7).
8. New subsections (h)(1)-(h)(2)(B)2. refiled 2-11-97 as an emergency, including amendment of Note; operative 2-11-97 (Register 97, No. 7). A Certificate of Compliance must be transmitted to OAL by 6-11-97 or emergency language will be repealed by operation of law on the following day.
9. Certificate of Compliance as to 2-11-97 order transmitted to OAL 6-10-97; disapproved by OAL and order of repeal as to 2-11-97 filed on 7-24-97 (Register 97, No. 30).
10. Certificate of Compliance as to 2-11-97 order, including amendment of section, resubmitted to OAL and approved on 7-24-97 (Register 97, No. 30).
11. Change without regulatory effect amending subsection (k)(10) filed 7-1-2004 pursuant to section 100, title 1, California Code of Regulations (Register 2004, No. 27).
12. Amendment of subsections (h)(1) and (h)(2)(B)1. filed 5-6-2024; operative 7-1-2024 (Register 2024, No. 19).