(a) The owner or operator of a facility with process vents associated with distillation, fractionation, thin-film evaporation, solvent extraction, or air or steam stripping operations managing hazardous wastes organic concentrations of at least 10 ppmw shall either:
- (1) reduce total organic emissions from all affected process vents at the facility below 1.4 kg/h (3 lb/h) and 2.8 Mg/yr (3.1 tons/yr); or
- (2) reduce, by use of a control device, total organic emissions from all affected process vents at the facility by 95 weight percent.
- (b) If the owner or operator installs a closed-vent system and control device to comply with the provisions of subsection (a) of this section the closed-vent system and control device shall meet the requirements of Section 66264.1033.
- (c) Determinations of vent emissions and emission reduction or total organic compound concentrations achieved by add-on control devices shall be based on engineering calculations or performance tests. If performance tests are used to determine vent emissions, emission reductions, or total organic compound concentrations achieved by add-on control devices, the performance tests shall conform with the requirements of Section 66264.1034(c).
- (d) When an owner or operator and the Department do not agree on determinations of vent emissions and/or emission reductions or total organic compound concentrations achieved by add-on control devices based on engineering calculations, the procedures in Section 66264.1034(c) shall be used to resolve the disagreement.