Cal. Code Regs. tit. 22, § 60688
(g) Any additional monitoring parameters that the local jurisdiction determines are necessary to demonstrate how the OTNWS will operate as designed.
Table60688-1. Continuous process verification monitoring parameters for reporting
Treatment Process
Parameter
Units
Reporting parameter
MBR
Effluent turbidity
NTU
Daily maximum, Rolling 24-hour 95th percentile
UV disinfection
Influent turbidity
NTU
Daily maximum, Rolling 24-hour 95th percentile
UV disinfection
Ultraviolet dose
mJ/cm2
Daily minimum
UV disinfection
Ultraviolet transmittance
%
Daily minimum
Chlorine disinfection
Flow rate
Gpm
Daily minimum, daily maximum
Chlorine disinfection
Influent chlorine dose
mg/L
Daily minimum
Chlorine disinfection
Effluent free chlorine residual
mg/L
Daily minimum
Chlorine disinfection
Influent ammonia
mg/L
Daily maximum
Chlorine disinfection
Influent turbidity
NTU
Daily maximum
Chlorine disinfection
Influent pH
Standard units
Daily maximum
Chlorine disinfection
Influent water temperature
°C or °F
Daily minimum
Membrane filtration
Effluent turbidity
NTU
Daily maximum, Rolling 24-hour 95th percentile
OTNWS monitoring results must be reported to the local jurisdiction in a format approved by the local jurisdiction at least quarterly. The monitoring report must include the following information:
Note: Authority cited: Sections 13558 and 13558.1, Water Code; and Sections 116271 and 116350, Health and Safety Code. Reference: Sections 13558 and 13558.1, Water Code.
1. New section filed 4-22-2026; operative 4-22-2026 pursuant to Water Code section 13558(f) (Register 2026, No. 17).