Cal. Code Regs. tit. 22, § 60632
(a) An OTNWS must use one of the pathogen control treatment trains prescribed in Table 60632-1 meeting the corresponding specification for each treatment process described in subsections (b) through (e) and must be capable of demonstrating the log reduction targets pursuant to section 60642.
Table 60632-1. Pathogen control treatment train for untreated alternate water sources
Pathogen control treatment train
Untreated alternate water source
Train A: MBR - UV - Chlorination
Onsite wastewater, stormwater, graywater, roof runoff
Train B: MBR - UV - Chlorination
Stormwater, graywater, roof runoff
Train C: MBR - UV - Chlorination
Graywater, roof runoff
Train D: MBR - UV
Graywater, roof runoff
Train E: Membrane filtration - UV - Chlorination
Graywater, roof runoff
Train F: UV
Roof runoff
(e) Membrane filtration process must use a microfiltration, ultrafiltration, nanofiltration, or reverse osmosis membrane so that the turbidity of the filtrate does not exceed any of the following:
Note: Authority cited: Sections 13558 and 13558.1, Water Code; and Sections 116271 and 116350, Health and Safety Code. Reference: Sections 13558 and 13558.1, Water Code.
1. New section filed 4-22-2026; operative 4-22-2026 pursuant to Water Code section 13558(f) (Register 2026, No. 17).