Cal. Code Regs. tit. 22, § 64575
(d) Newly installed flushing valves and blowoffs shall be designed to maintain the minimum continuous flushing flows as indicated below to produce a minimum velocity of 2.5ft/s in commonly used sizes of pipe.
Table 64575-A. Minimum Flushing Flows for Different Size Water Mains.
Nominal Main Size Diameter (inches)
Minimum Flushing Flow (gallons per minute)
2
25
3
50
4
100
6
225
8
400
10
600
12
900
14
1200
16
1600
Note: Authority cited: Sections 116350, 116375 and 131200, Health and Safety Code. Reference: Sections 116275, 116375, 116535 and 131051, Health and Safety Code.
1. New section filed 2-8-2008; operative 3-9-2008 (Register 2008, No. 6).
2. Change without regulatory effect amending subsection (a) filed 4-21-2011 pursuant to section 100, title 1, California Code of Regulations (Register 2011, No. 16).