Cal. Code Regs. tit. 22, § 64570
(a) All newly installed water mains shall comply with the materials and installation standards of the American Water Works Association pursuant to tables 64570-A and 64570-B. The standards are hereby incorporated by reference.
Table 64570-A Materials Standards for Water Mains
Type of Material
Diameter of Main
Applicable Standard
PVC
4 in. through 12 in.
C900-97
PVC
14 in. through 48 in.
C905-97
Polyethylene (HDPE)
4 in. through 63 in.
C906-99
Fiberglass
All sizes
C950-01
Ductile Iron
All sizes
C150/A21.50-02
Ductile Iron, Centrifugally cast
All sizes
C151/A21.51-02
Steel
6 inches and larger
C200-97
Copper
All sizes
C800-05
Concrete
Reinforced steel-cylinder
All sizes
C300-04
Prestressed steel-cylinder
All sizes
C301-99,
C304-99
Reinforced noncylinder
All sizes
C302-04
Bar wrapped/steel cylinder
All sizes
C303-02
PVC, Molecularly oriented polyvinyl chloride
All sizes
C909-02
Table 64570-B Installation Standards for Water Mains
Type of Installation
Applicable Standard
Steel Pipe-Design and Installation
M-11 (2004)
Ductile-Iron Water Mains and Their Appurtenances
C600-05
Underground Installation of PVC Pressure Pipe and Fittings
C605-05
Concrete Pressure Pipe
M9(1995)
(b) Water mains shall:
Note: Authority cited: Sections 116350, 116375 and 131200, Health and Safety Code. Reference: Sections 116275, 116375, 116535 and 131051, Health and Safety Code.
1. Amendment filed 10-9-85; effective thirtieth day thereafter (Register 85, No. 42).
2. New article 4 (sections 64570-64578) and repealer and new section filed 2-8-2008; operative 3-9-2008 (Register 2008, No. 6).