Cal. Code Regs. tit. 22, § 64413.1
(a) Each water treatment facility shall be classified pursuant to Table 64413.1-A based on the calculation of total points for the facility using the factors specified in subsection (b).
Table 64413.1-A. Water Treatment Facility Class Designations
Total Points
Class
Less than 20
T1
20 through 39
T2
40 through 59
T3
60 through 79
T4
80 or more
T5
(b) The calculation of total points for each water treatment facility shall be the sum of the points derived in each of paragraphs (1) through (13). If a treatment facility treats more than one source, the source with the highest average concentration of each contaminant shall be used to determine the point value in paragraphs (2) through (5).
(1) For water source, the points are determined pursuant to Table 64413.1-B.
Table 64413.1-B. Points for Source Water Used by the Facility
Type of source water used by the facility
Points
Groundwater and/or purchased treated water meeting primary and secondary drinking water standards, as defined in section 116275 of the Health and Safety Code
2
Water that includes any surface water or groundwater under the direct influence of surface water
5
(2) For influent microbiological water quality, points shall be determined by using the median of all total coliform analyses completed in the previous 24 months pursuant to Table 64413.1-C:
Table 64413.1-C. Influent Water Microbiological Quality Points
Median Coliform Density Most Probable Number Index (MPN)
Points
less than 1 per 100 mL
0
1 through 100 per 100 mL
2
greater than 100 through 1,000 per 100 mL
4
greater than 1,000 through 10,000 per 100 mL
6
greater than 10,000 per 100 mL
8
(3) For facilities treating surface water or groundwater under the direct influence of surface water, points for influent water turbidity shall be determined pursuant to Table 64413.1-D on the basis of the previous 24 months of data, except that if turbidity data is missing for one or more of the months, the points given for turbidity shall be 5. The maximum influent turbidity sustained for at least one hour according to an on-line turbidimeter shall be used unless such data is not available, in which case, the maximum influent turbidity identified by grab sample shall be used. For facilities that have not been in operation for 24 months, the available data shall be used. For facilities whose permit specifies measures to ensure that influent turbidity will not exceed a specified level, the points corresponding to that level shall be assigned.
Table 64413.1-D. Influent Water Turbidity Points
Maximum Influent Turbidity Level Nephelometric Turbidity Units (NTU)
Points
Less than 15
0
15 through 100
2
Greater than 100
5
(4) The points for influent water perchlorate, nitrate, or nitrite levels shall be determined by an average of the three most recent sample results, pursuant to Table 64413.1-E.
Table 64413.1-E. Influent Water Perchlorate, Nitrate, and Nitrite Points
Perchlorate, Nitrate, and Nitrite Data Average
Points
Less than or equal to the maximum contaminant level (MCL), as specified in Table 64431-A
0
For each contaminant greater than its MCL
5
(5) The points for other influent water contaminants with primary MCLs shall be a sum of the points for each of the inorganic contaminants (Table 64431-A), organic contaminants (Table 64444-A) and radionuclides (Tables 64442 and 64443). The points for each contaminant shall be based on an average of the three most recent sample results, pursuant to Table 64413.1-F. If monitoring for a contaminant has been waived pursuant to sections 64432(m) or (n), 64432.2(c), or 64445(d), the points shall be zero for that contaminant.
Table 64413.1-F. Influent Water Chemical and Radiological Contaminant Points
Contaminant Data Average
Points
Less than or equal to the MCL
0
Greater than the MCL
2
5 Times the MCL or greater
5
(6) The total points for surface water filtration treatment shall be the sum of the points of those treatment processes utilized by the facility for compliance with section 64652, pursuant to Table 64413.1-G.
Table 64413.1-G. Points for Surface Water Filtration Treatment
Treatment
Points
Conventional, direct, or inline
15
Diatomaceous earth
12
Slow sand, membrane, cartridge, or bag filter
8
Backwash recycled as part of process
5
(10) The total points for disinfection treatment shall be the sum of the points for those treatment processes utilized by the facility for compliance with section 64654(a), pursuant to Table 64413.1-H.
Table 64413.1-H. Points for Disinfection Treatment
Treatment Process
Points
Ozone
10
Chlorine and/or chloramine
10
Chlorine dioxide
10
Ultra violet (UV)
7
(11) The points for disinfection/oxidation treatment not included in paragraphs (6), (7), (8), or (10) shall be a sum of the points for all the treatment processes used at the facility pursuant to Table 64413.1-I.
Table 64413.1-I. Points for Disinfection/Oxidation Treatment without Inactivation Credit
Treatment Process
Points
Ozone
5
Chlorine and/or chloramine
5
Chlorine dioxide
5
Ultra violet (UV)
3
Other oxidants
5
Note: Authority cited: Sections 106910 and 131200, Health and Safety Code. Reference: Sections 106875, 106910, 116555, 131050 and 131051, Health and Safety Code.
1. New section filed 12-26-2000 as an emergency; operative 1-1-2001 (Register 2000, No. 52). A Certificate of Compliance must be transmitted to OAL by 5-1-2001 or emergency language will be repealed by operation of law on the following day.
2. New section refiled 4-25-2001 as an emergency; operative 5-2-2001 (Register 2001, No. 17). A Certificate of Compliance must be transmitted to OAL by 8-30-2001 or emergency language will be repealed by operation of law on the following day.
3. Certificate of Compliance as to 4-25-2001 order transmitted to OAL 7-12-2001 and filed 8-13-2001 (Register 2001, No. 33).
4. Amendment of subsections (b)(4)-(5), (b)(7) and (b)(13) and amendment of Note filed 9-18-2007; operative 10-18-2007 (Register 2007, No. 38).
5. Amendment of subsections (b), (b)(4) -- Table 64413.1-E and (b)(5) and amendment of Note filed 10-29-2008; operative 11-28-2008 (Register 2008, No. 44).