Cal. Code Regs. tit. 19, § 575.3
(a) Maintenance procedures shall include a thorough examination of the three basic elements of an extinguisher:
(3) expelling means
Exception: During annual maintenance, it is not necessary to internally examine the following extinguisher types:
7. Water mist type
However, such extinguishers shall be thoroughly examined externally in accordance with the applicable items of 575.3(a)(1) and Table 4.
(b) Fire extinguishers shall be thoroughly examined externally and the appropriate corrective action performed in accordance with the applicable items of Table 4, External Examination Maintenance Checkpoints.
(c) Fire extinguishers shall be weighed on accurate scales, as defined in 557.1(a), and it shall be verified that the total weight is within the allowable tolerances specified by the manufacturer.
Exception: Water-type and wet chemical fire extinguishers that have the liquid amount specified on the extinguisher shell, a fill level mark or an anti-overfill tube.
Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.
1. New section filed 3-4-92; operative 4-3-92 (Register 92, No. 15).
2. Repealer and new section filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
3. Amendment of subsection (a) Exception filed 11-21-2002; operative 1-1-2003 (Register 2002, No. 47).
4. Change without regulatory effect amending Exception to subsection (a)(3) filed 7-25-2006 pursuant to section 100, title 1, California Code of Regulations (Register 2006, No. 30).
5. Amendment of subsection (c) and new subsections (d) and (e) filed 2-28-2007; operative 3-30-2007 (Register 2007, No. 9).
6. Amendment filed 7-17-2013; operative 10-1-2013 (Register 2013, No. 29).