Cal. Code Regs. tit. 19, § 568
(b) Certain smaller fire extinguishers which are charged with a multipurpose dry chemical or halogenated agent are rated on Class B and Class C fires, but having insufficient effectiveness to earn the minimum 1-A rating even though they have value in extinguishing smaller Class A fires. They shall not be used to meet the requirements of Table 2.
Table 2
Light (Low) Hazard Occupancy
Ordinary (Moderate) Hazard Occupancy
Extra (High) Hazard Occupancy
Minimum rated single extinguisher
2-A
2-A
4-A*
Maximum floor area per unit of A
3,000 sq ft
1,500 sq ft
1,000 sq ft
Maximum floor area for extinguisher
11,250 sq ft
11,250 sq ft
11,250 sq ft
Maximum travel distance to extinguisher
75 ft
75 ft
75 ft
* Two 2 ½ gal (9.46 L) water type extinguishers can be used to fulfill the requirement of one 4-A rated extinguisher.
Note: 1 ft = 0.305 m
1 sq ft = 0.0929 m2
Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.