(a) In order to determine if the owner or operator of a tank facility is following the SPCC Plan, a routine inspection shall include verification of the following measures:
- (1) The SPCC Plan elements are consistent with HSC Section 25270.4.5.
- (2) The SPCC Plan, including any amendments, is complete and appropriate for the tank facility.
- (3) The SPCC Plan has been certified by the owner or operator, or a professional engineer if required by the Code of Federal Regulations, Title 40, Part 112.
- (4) The SPCC Plan has been reviewed by the owner or operator at least once every five years, and the review is documented.
- (5) The appropriate containment and/or diversionary structures or equipment are provided.
- (6) The owner or operator has completed and documented the periodic inspections and applicable tests in accordance with the frequency specified in their SPCC Plan.
- (7) The training and discharge prevention briefings are conducted. Records of the training and discharge prevention briefings are documented for a minimum of 3 years. Records of training and discharge prevention briefing kept under usual and customary business practices will suffice for purposes of this subsection.
- (8) The visible discharges from aboveground storage tanks have been promptly corrected and accumulations of petroleum in diked areas are promptly removed.
- (b) Section 1611 shall not apply to an inspection of a tank facility that meets the requirements of HSC Section 25270.4.5(b).
Note: Authority cited: Section 25270.4.1, Health and Safety Code. Reference: Section 25270.4.5, Health and Safety Code.