Cal. Code Regs. tit. 19, § 3.29
(c) Group A Occupancies.
(1) One additional Class 2-A unit shall be provided in Group A Occupancies as follows:
(A) On each side of the stage or platform.
Exception: Platforms 1000 square feet or less in area need have only one such extinguishing unit.
(2) Not less than one 10-B: C unit (not less than 4-B: C for existing extinguishers in existing occupancies) shall be provided:
(C) For each motion picture machine in projection rooms.
Exception: One 20-B:C unit (not less than 8-B:C for existing extinguishers in existing occupancies) in each projection room may be accepted as providing substantially equal protection.
(d) Group R-2.1, R-3.1 and R-4 Occupancies. In Group R-2.1, R-3.1 and R-4 Occupancies a continuously attached garden hose, equipped with a water flow control nozzle, may be provided in lieu of one or more required fire extinguishers when acceptable to the enforcing agency. The location and length of such hose shall be as designated or approved by the enforcing agency.
Note: It is recommended that wherever possible portable fire extinguishers be located adjacent to manual fire alarm sending stations.
Note: Authority cited: Sections 13108, 13143, 13143.6, 13211, 17920.7, 17921 and 18897.3, Health and Safety Code. Reference: Sections 13100-13143.6, 13210-13216, 17920.7, 17921 and 18897-18897.7, Health and Safety Code.
1. Change without regulatory effect of Note filed 8-24-88 (Register 88, No. 36).
2. Change without regulatory effect amending subsection (d) filed 2-25-2003 pursuant to section 100, title 1, California Code of Regulations (Register 2003, No. 9).
3. Change without regulatory effect amending subsection (a) filed 7-25-2006 pursuant to section 100, title 1, California Code of Regulations (Register 2006, No. 30).
4. Amendment of subsections (a) and (d) filed 1-12-2011; operative 1-12-2011 pursuant to Government Code section 11343.4 (Register 2011, No. 2).