Cal. Code Regs. tit. 17, § 95387
Requirements to Prepare Retrofit or Retirement Plans for Facilities with Leaking Stationary Refrigeration Systems.
Effective Nov 19, 2010Register 2010, No. 43Authority cited: Sections 38501, 38510, 38560, 38562, 38563, 38580, 38597, 39600, 39601 and 41511, Health and Safety Code. Reference: Sections 38501, 38505, 38510, 38560, 38562, 38563, 38580, 38597, 39600, 39601 and 41511, Health and Safety Code.State of California
(a) Retrofit or Retirement Plan Requirements.
- (1) After January 1, 2011, the owner or operator of a refrigeration system with a refrigerant leak that has not been successfully repaired within the time required for refrigerant leak repair under subsection (b), (c), or (d) of section 95386 must prepare and implement a dated retrofit or retirement plan as provided in section 95386(g). The plan must establish a schedule to retrofit or retire a leaking refrigeration system no later than six months after the initial detection of the refrigerant leak, and all work must be completed during this six-month period.
(2) The retrofit or retirement plan must be kept at the site of the refrigeration system with a refrigerant leak. If a refrigeration system is to be retired and replaced, the plan must include information required under this subsection specific to the new refrigeration system to be constructed or installed. If a refrigeration system is to be retrofitted, the plan must include information required under this subsection specific to the refrigeration system after the retrofit has been completed. A retrofit or retirement plan must include the following information:
- (A) The system identification number of the refrigeration system being retired or retrofitted.
- (B) Equipment type.
- (C) Equipment manufacturer.
- (D) Equipment model or description.
- (E) Intended physical location of the refrigeration system through schematic or floor plan with locations clearly noted.
- (F) Temperature classification -- The refrigeration system must be identified as a low temperature system, a medium temperature system, or other.
- (G) Full charge of the refrigeration system.
- (H) Type of high-GWP refrigerant(s) used.
- (I) If a refrigeration system is to be retired and replaced, a plan to dispose of the retired refrigeration system.
(J) A timetable which includes, at a minimum:
- 1. the date installation, construction, or retrofit of the refrigeration system is expected to begin, and
- 2. the expected completion date of the installation, construction, or retrofit of the refrigeration system.
- (K) A signature by a representative of the facility, including the date signed.
- (b) Retrofit or Retirement Plan Requirements During System Mothballing. The retrofit or retirement requirements of this section shall not apply during the time that a refrigeration system is undergoing or is in system mothballing. The retrofit or retirement requirements of this section shall apply on the day that the refrigeration system resumes operation at a facility.
- (c) Retrofit or Retirement Plan Requirements Exemption. If the owner or operator of a refrigeration system has received an exemption from the Executive Officer pursuant to section 95397, the preparation and implementation of a retrofit or retirement plan is not required during the time period the exemption is in effect. If the owner or operator of a refrigeration system has submitted a request for an exemption pursuant to section 95397, the preparation and implementation of a retrofit or retirement plan is not required until a final exemption determination is made by the Executive Officer. A written record(s) must be kept pursuant to section 95389 to document that the owner or the operator has requested or received an exemption.
Note: Authority cited: Sections 38501, 38510, 38560, 38562, 38563, 38580, 38597, 39600, 39601 and 41511, Health and Safety Code. Reference: Sections 38501, 38505, 38510, 38560, 38562, 38563, 38580, 38597, 39600, 39601 and 41511, Health and Safety Code.