- (a) All production facilities storing and/or processing fluids, except valves, headers, manifolds, pumps, compressors, wellheads, pipelines, flowlines and gathering lines shall have secondary containment.
- (b) Secondary containment shall be capable of containing the equivalent volume of liquids from the single piece of equipment with the largest gross capacity within the secondary containment.
- (c) Secondary containment shall be capable of confining liquid for a minimum of 72 hours.
- (d) When not in use for rain water management, rain water valves on a secondary containment shall be closed and secured to prevent unauthorized use.
- (e) All damage to secondary containment shall be repaired immediately.
- (f) The requirements of this section are not applicable until six months after the effective date of this regulation.
Note: Authority cited: Sections 3013 and 3270, Public Resources Code. Reference: Sections 3106 and 3270, Public Resources Code.
History
1. New section filed 12-30-2010; operative 1-29-2011 (Register 2010, No. 53).