(a) Diaphragm meters under five hundred cubic feet per hour (500 CFH).
(1)
- (A) Meters shall be tested for accuracy and adjusted, if necessary, to acceptable limits at least once every ten (10) years.
- (B) Accuracy limits shall be one hundred percent (100%) plus or minus five-tenths of a percent (±0.5%).
- (C) New meters accompanied by a certified test certificate are not required to be tested if the test results on the certificate are within accuracy limits.
(2)
- (A) Meters shall be tested at both low and high flow rates.
- (B) Low flow rate shall be at twenty to forty percent (20% – 40%) of capacity.
- (C) High flow rate shall be at eighty to one hundred twenty percent (80% – 120%) of capacity.
- (D) Numerical accuracy difference between the two (2) rates shall not exceed one percent (1%).
- (3) Meters shall be tested by a slow-motion type or pilot-burner type of test after any repairs.
(b) Diaphragm meters over five hundred cubic feet per hour (500 CFH).
(1) New and shop-repaired meters.
- (A)
(i) Shop-repaired meters and new meters not accompanied by a certified test certificate shall be tested for accuracy and, if necessary, adjusted to acceptable limits.
(ii) Accuracy limits shall be one hundred percent (100%) plus or minus one percent (±1%).
- (iii) New meters accompanied by a certified test certificate are not required to be tested if the test results on the certificate are within accuracy limits.
(B)
- (i) Meters shall be tested at both low and high flow rates.
- (ii) Low flow rate shall be at twenty to forty percent (20% – 40%) of capacity.
- (iii) High flow rate shall be at eighty to one hundred twenty (80% – 120%) percent of capacity.
- (iv) The numerical accuracy difference between the values for the two (2) rates shall not exceed one percentage point (1%).
(2) In-service meters.
(A)
- (i) Meters shall be tested for accuracy and, if necessary, adjusted to acceptable limits at least once every five (5) years.
- (ii) Accuracy limits shall be one hundred percent (100%) plus or minus two percent (±2%).
(B)
- (i) Meters shall be tested at both low and high flow rates.
- (ii) Low flow rate shall be at twenty to forty percent (20% – 40%) of capacity.
- (iii) High flow rate shall be at eighty to one hundred twenty percent (80% – 120%) of capacity.
- (iv) The numerical accuracy difference between the values for the two (2) rates shall not exceed two percentage points (2%).
- (c) Orifice meters.
- (1) Periodic inspections. Meters must be inspected by qualified personnel at periodic intervals to ensure all elements and associated facilities function accurately.
- (2) Visual inspection. To verify the operation of the meter device, a visual inspection of the metering station shall be performed each time the chart is changed.
(3) Inspection and calibration.
- (A) An inspection and calibration shall be performed semi-annually on the orifice meters, orifice plates, and installed auxiliary elements of the metering station.
- (B) Meters shall be maintained to an accuracy of one hundred percent (100%) plus or minus two percent (±2%).
(C) Any components not functioning properly shall be repaired or replaced.
- (d) Rotary meters.
- (1) Meters shall be tested for accuracy and, if necessary, adjusted to acceptable limits at least once every five (5) years.
- (2) Accuracy limits shall be one hundred percent (100%) plus or minus one percent (±1%) at approximately twenty to one hundred percent (20% – 100%) of the meter's rated capacity.
- (3) New meters accompanied by a certified test certificate are not required to be tested if the test results on the certificate are within the accuracy limits.
(e) Turbine meters.
- (1) Meters shall be tested for accuracy and, if necessary, adjusted to acceptable limits at least once every five (5) years.
- (2) Meters shall be maintained to an accuracy of one hundred percent (100%) plus or minus one percent (±1%).
- (3) New meters accompanied by a certified test certificate are not required to be tested if the test results on the certificate are within the accuracy limits.
(f) Meter correcting instruments.
(1)
- (A) Pressure correcting instruments or devices may be used where the pressure exceeds the normal delivered pressure.
- (B) However, calculated pressure factors may be used if delivered pressure is relatively constant.
(2)
- (A) Each base pressure and base volume correcting device shall be tested for accuracy each time the associated meter is tested.
- (B) This requirement does not apply to constant pressure compensating indexes.
Codification Notes: This section was promulgated as Rule 7.04 of the Special Rules — Gas prior to codification in the Code of Arkansas Rules.