- (a) Impairments, critical deficiencies, and noncritical deficiencies, as described in NFPA 25 and its Table E.1, warrant a yellow tag.
(b) An RME or inspector who finds an impairment, critical deficiency, or noncritical deficiency must:
- (1) Hang a yellow tag;
- (2) Notify the building owner; and
(3)
- (A) Send the inspection report to the AHJ.
- (B) This information must be sent by mail or fax within fourteen (14) business days of inspection.
Codification Notes: NFPA 25 is the Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems produced by the National Fire Protection Association.