- (a) A fitter is responsible for fulfilling the responsibilities described in the definition of “fitter” and in this part.
(b) The fitter is responsible for installing the sprinkler system in accordance with:
- (1) Drawings approved by the firm’s RME; and
- (2) All applicable rules, codes, and standards.
- (c) At least one (1) licensed fitter shall be onsite when a fire protection sprinkler system is being installed or serviced.
(d) Once an installation is complete, the fitter:
- (1) Shall perform testing and provide documentation for such testing in accordance with the appropriate NFPA standard; and
(2) Is responsible for:
- (A) Completing the Contractor’s Material and Test Certificate in accordance with the appropriate NFPA standard; and
- (B) Attaching the permanent green installation tag.
Codification Notes: “Fitter” is defined in 20 CAR § 901-106.