All appliances required for electric steam generators shall be attached in accordance with the following rules:
(1)
- (A) A cable at least as large as one of the incoming power lines to the generator shall be provided for grounding the generator shell.
- (B) This cable shall be permanently fastened on some part of the generator and shall be grounded in an approved manner;
(2)
- (A) A suitable screen or guard shall be provided around high-tension bushings and a sign posted warning of high voltage.
- (B) This screen or guard shall be so located that it will be impossible for anyone working around the generator to accidentally come in contact with the high-tension circuits; and
(3)
- (A) The minimum safety valve or safety relief valve capacity for electric boilers shall be three and one-half pounds per hour per kilowatt (3 1/2 lbs./hr/kW) (one and six-tenths kilograms per hour per kilowatt (1.6 kg/hr/kW)) input.
- (B) The pressure setting shall not be higher than the maximum allowable working pressure on the completed boiler.