(a) Egress policies.
- (1) The ASCU shall develop policies and procedures to deal with residents who wander or may wander.
(2) The procedures shall include actions to be taken by the facility to:
- (A) Identify missing residents;
- (B) Notify all individuals or institutions that require notification under law or rule when a resident is missing; and
- (C) Attempt to locate the missing resident.
(b) Locking devices.
(1) All locking devices used on exit doors shall:
- (A) Be approved by the Office of Long-Term Care, building code agencies, and the fire marshal having jurisdiction over the facility;
- (B) Be electronic; and
- (C) Release upon activation of the fire alarm or sprinkler system.
- (2) If the unit uses keypads to lock and unlock exits, directions for the keypad's operation to allow entrance shall be posted on the outside of the door.
- (3) The keypads and locks shall meet the requirements under IBC applicable to Level II assisted living facilities.
- (4) Staff shall be trained in all methods of releasing or unlocking the locking device.
Codification Notes: “IBC” means International Building Code.