20 CAR § 400-804
(a)
(1) All institutions licensed under these standards shall be designated and constructed to substantially comply with pertinent local and state:
(b) Plans shall be submitted to the Division of Provider Services and Quality Assurance in the following stages:
(2) Final submission.
(i) Working drawings and specifications which shall be well prepared so that clear and distinct prints may be obtained.
(ii) Accurate dimensions and including all necessary explanatory notes, schedules, and legends.
(iii) Working drawings shall be complete and adequate for contract purposes.
(a)
(b) (b) Plan of each floor and roof;
(c) (c) Elevations of each façade;
(f) (f) Schedule of finishes.
(B) Step 2. Equipment drawings. Large scale drawings of typical and special rooms indicating all fixed equipment and major items of furniture and movable equipment.
(C) Step 3. Structural drawings.
(b) (b) Schedule of beams, girders, and columns shall be included.
(ii) Floor levels, column centers, and offsets shall be dimensioned.
(iii) Special openings and pipe sleeves shall be dimensioned or otherwise noted for easy reference.
(D) Step 4. Mechanical drawings. The drawings with specifications shall show the complete heating, steam piping and ventilation systems, plumbing, drainage and standpipe system, and laundry.
(b) (b) Heating and steam mains and branches with pipe sizes;
(c) (c) Sizes, types, and heating surfaces of boilers, furnaces, with stokers and oil burners, if any;
(g) (g) Air quantities for all room supply and exhaust ventilating duct openings.
(b) (b) Locations and size of soil, waste, and vent stacks with connections to house drains, clean outs, fixtures, and equipment;
(c) (c) Size and location of hot, cold and circulating mains, branches and risers from the service entrance and tanks;
(f) (f) Plumbing fixtures and equipment which require water and drain connections.
(iii) Elevators and dumbwaiters. Details and dimensions of shaft, pit and machine room, sizes of car platform, and doors.
(b) (b) These shall be detailed at a satisfactory scale to show the location, size, and connections of all fixed equipment.
(E) Step 5. Electrical drawings.
(i) Drawings shall show all electrical wirings, outlets, smoke detectors, and equipment which require electrical connections.
(b) (b) Duty stations;
(c) (c) Door signal lights;
(e) (e) Wiring diagrams.
(vi) Fire alarm system with stations, signal devices, control board and wiring diagrams.
(F) Step 6. Specifications. Specifications shall supplement the drawings to fully describe types, sizes, capacities, workmanships, finishes, and other characteristics of all materials and equipment and shall include the following:
Codification Notes: “NFPA” means National Fire Protection Association.