(a)
- (1) Nurses' stations shall be provided and so designated that they contain a minimum of sixty square feet (60 sq. ft.) per each thirty-five-bed patient unit, and are not more than one hundred twenty linear feet (120 LF) from each patient room.
(2) The station shall include:
- (A) Adequate storage and preparation area or areas;
- (B) Medication;
- (C) Toilet and hand-washing facilities; and
- (D) Sufficient lighting.
(b)
- (1) A separate utility room shall be provided for clean items and soiled items for each nurses' station.
- (2) They shall be mechanically ventilated to the outside and adequately lighted.
- (3) Two (2) or more electrical convenience outlets shall be provided for each utility room.
- (4) Blade handle control faucets shall be provided.
- (5) Gooseneck spouts shall be in a separate room and ventilated to the outside.
(c)
- (1) A closet for soiled linens shall be provided for each nurses' station.
- (2) This dirty linen storage shall be in a separate room and ventilated to the outside.