(a) Lighting.
- (1) Approaches to buildings and parking lots and all occupied spaces within buildings shall have fixtures that can be illuminated as necessary.
- (2) Patient rooms shall have general lighting and night lighting.
- (3) Nursing unit corridors shall have general illumination with provisions for reducing light levels at night.
- (4) Egress and exit lighting shall comply with NFPA 101.
(b) Nurse/patient communication station.
- (1) A nurse/patient communication system shall be provided for each patient bedside in accordance with the functional program.
(2) An emergency call system shall be provided in each patient’s:
- (A) Toilet;
- (B) Bath; and
- (C) Shower room.
- (c) Emergency electrical generators shall have a minimum forty-eight (48) hours of onsite fuel.
- (d) All healthcare occupancies shall be provided with a fire alarm system in accordance with NFPA 101 and NFPA 72.