20 CAR pt. 41, Appendix B
TABLE 1
| Filter Efficiencies for Central Ventilation and Air Conditioning Systems in Health Care Facilities | |||
|---|---|---|---|
| Area Designation | No. Filter Beds | Filter Bed No.1 (%) | Filter Bed No.21 (%) |
| All areas for patient care, treatment, and diagnosis, and those areas providing direct service or clean supplies such as sterile and clean processing. | 2 | 30 | 90 |
| Protective Environment Room 2 | 2 | 30 | 99.97 |
| Laboratories | 1 | 80 | - |
| Administrative, Bulk Storage, Soiled Holding Areas, Food Preparation Areas, and Laundries | 1 | 30 | - |
These requirements do not apply to small outpatient clinics or outpatient clinics that do not perform invasive applications or procedures.
Notes: The filtration efficiency ratings are based on average dust spot efficiency per ASHRAE 52.1 – 1992.
Additional roughing or prefilters should be considered to reduce maintenance required for filters with efficiencies higher than 75 percent.