(a)
(1) Air/vacuum relief valves provide a means for releasing air at the start of a dose cycle so the system will:
- (A) Charge quickly with wastewater; and
- (B) Allow air to enter the system quickly at the end of the dose cycle.
(2) Air/vacuum valves shall be located at the highest points of either:
- (A) Supply or return manifolds; or
- (B) Both.
(b)
- (1) Air/vacuum relief valves shall be sized based on the proposed design flow rate.
- (2) A valve that is undersized will not provide an adequate amount of airflow.
- (c) A Schrader valve shall be provided at each vacuum valve as a means of checking the pressure of the drip field.