(a)
- (1) A flow meter shall be installed after the filter system but before the drip dispersal field.
- (2) The flow meter shall incorporate not only a rate-of-flow gauge but also a “total gallons pumped” register.
- (3) The flow-rate gauge and “total gallons pumped” register may be separate devices.
(4) The flow meter shall be installed in a protective box that will be of sufficient size:
- (A) For servicing the meter; and
- (B) To allow easy access for reading the meter.
- (5) The flow meter shall be sized for the dispersal flow as well as the additional field flushing volume.
(b)
(1) Pressure gauges shall be located:
- (A) Before the filter;
- (B) After the filter; and
- (C) On the dispersal field return line.
- (2) Pressure gauges shall be enclosed in the headworks box that allows easy access for observation.
(3) The gauges shall be:
- (A) Liquid-filled; and
- (B) A minimum of three inches (3”) in diameter.
- (4) The pressure range of the gauge shall be sufficient for the maximum pressure that will be expected in the system.