(a) Where used, multiple occupancy sleeping rooms will provide:
- (1) The ability for observation by staff;
- (2) A minimum floor area of thirty-five square feet (35 ft2) per detainee in the sleeping area;
- (3) Minimum clear floor-to-ceiling height of eight feet (8' 0") where room contains ten (10) or fewer detainees and nine feet (9’ 0”) where room contains eleven (11) or more detainees; and
- (4) Beds above floor level.
- (b) In addition to the foregoing requirements, multiple occupancy housing areas shall also adhere to all requirements contained in 12 CAR § 50-1616.