The electrical plans submitted pursuant to Rule 535-X-11-.07 of this chapter must:
- (a) Provide plan and detail of service equipment, including service entrance, conductors, service raceway and clearances above ground and above structures.
- (b) Indicate method and detail for ground service equipment.
- (c) Provide a single line diagram of the entire electrical installation.
- (d) Provide complete load calculations for service and feeders.
- (e) Identify and show sizes of all feeders and branch circuits.
- (f) Show size, rating, and location of main disconnect/over-current protective devices.
- (g) Detail method of interconnection between modules or units and location of connections.
- (h) Show location of all outlets and junction boxes.
- (i) Indicate how nonmetallic-sheathed cable in locations subject to mechanical damage is to be protected.
- (j) Indicate method of backing mounting and stapling of fixtures and wiring.
- (k) Provide details showing mounting of nontypical fixtures, if any.
- (l) Provide name plate rating of all appliances and equipment.
- (m) Indicate method of testing.
- (n) Indicate that all wiring, fixtures, and equipment are listed or labeled.
Author: Harold A. Hendrix
Statutory Authority: Code of Ala. 1975, §§24-4A-3, 24-6-4.
History: Filed February 6, 1990.