Ala. Admin. Code r. 335-7-6-.26
(1) Calculation of CT values.
(2) CT values for chlorine dioxide and ozone.
(a) Systems receive the Cryptosporidium treatment credit listed in this table by meeting the corresponding chlorine dioxide CT value for the applicable water temperature, as described in paragraph (1) of this rule.
| CT Values (mg•min/L) for Cryptosporidium Inactivation by Chlorine Dioxide1 |
| Log credit | Water Temperature, °C |
| <=0.5 | 1 | 2 | 3 | 5 | 7 | 10 | 15 | 20 | 25 | 30 | |
| 0.25 | 159 | 153 | 140 | 128 | 107 | 90 | 69 | 45 | 29 | 19 | 12 |
| 0.5 | 319 | 305 | 279 | 256 | 214 | 180 | 138 | 89 | 58 | 38 | 24 |
| 1.0 | 637 | 610 | 558 | 511 | 429 | 360 | 277 | 179 | 116 | 75 | 49 |
| 1.5 | 956 | 915 | 838 | 767 | 643 | 539 | 415 | 268 | 174 | 113 | 73 |
| 2.0 | 1275 | 1220 | 1117 | 1023 | 858 | 719 | 553 | 357 | 232 | 150 | 98 |
| 2.5 | 1594 | 1525 | 1396 | 1278 | 1072 | 899 | 691 | 447 | 289 | 188 | 122 |
| 3.0 | 1912 | 1830 | 1675 | 1534 | 1286 | 1079 | 830 | 536 | 347 | 226 | 147 |
1 Systems may use this equation to determine log credit between the indicated values: Log credit = [0.001506 x (1.09116)Temp] x CT
(b) Systems receive the Cryptosporidium treatment credit listed in this table by meeting the corresponding ozone CT values for the applicable water temperature, as described in paragraph (1) of this rule.
| CT Values (mg•min/L) for Cryptosporidium Inactivation by Ozone1 |
| Log credit | Water Temperature, °C |
| <=0.5 | 1 | 2 | 3 | 5 | 7 | 10 | 15 | 20 | 25 | 30 | |
| 0.25 | 6.0 | 5.8 | 5.2 | 4.8 | 4.0 | 3.3 | 2.5 | 1.6 | 1.0 | 0.6 | 0.39 |
| 0.5 | 12 | 12 | 10 | 9.5 | 7.9 | 6.5 | 4.9 | 3.1 | 2.0 | 1.2 | 0.78 |
| 1.0 | 24 | 23 | 21 | 19 | 16 | 13 | 9.9 | 6.2 | 3.9 | 2.5 | 1.6 |
| 1.5 | 36 | 35 | 31 | 29 | 24 | 20 | 15 | 9.3 | 5.9 | 3.7 | 2.4 |
| 2.0 | 48 | 46 | 42 | 38 | 32 | 26 | 20 | 12 | 7.8 | 4.9 | 3.1 |
| 2.5 | 60 | 58 | 52 | 48 | 40 | 33 | 25 | 16 | 9.8 | 6.2 | 3.9 |
| 3.0 | 72 | 69 | 63 | 57 | 47 | 39 | 30 | 19 | 12 | 7.4 | 4.7 |
1 Systems may use this equation to determine log credit between the indicated values: Log credit = [0.0397 x (1.09757)Temp] x CT
(4) Ultraviolet light. Systems receive Cryptosporidium, Giardia lamblia, and virus treatment credits for ultraviolet (UV) light reactors by achieving the corresponding UV dose values shown in subparagraph (4)(a) of this rule below. Systems must validate and monitor UV reactors as described in subparagraphs (4)(b) and (c) below to demonstrate that they are achieving a particular UV dose value for treatment credit.
(a) UV dose table. The treatment credits listed in this table are for UV light at a wavelength of 254 nm as produced by a low pressure mercury vapor lamp. To receive treatment credit for other lamp types, systems must demonstrate an equivalent germicidal dose through reactor validation testing, as described in subparagraph (4)(b) below. The UV dose values in this table are applicable only to post-filter applications of UV.
| UV dose table for Cryptosporidium, Giardia lamblia, and virus inactivation credit |
| Log credit | Cryptosporidium UV dose (mJ/cm^2) | Giardia lamblia UV dose (mJ/cm^2) | Virus UV dose (mJ/cm^2) |
| 0.5 | 1.6 | 1.5 | 39 |
| 1.0 | 2.5 | 2.1 | 58 |
| 1.5 | 3.9 | 3.0 | 79 |
| 2.0 | 5.8 | 5.2 | 100 |
| 2.5 | 8.5 | 7.7 | 121 |
| 3.0 | 12 | 11 | 143 |
| 3.5 | 15 | 15 | 163 |
| 4.0 | 22 | 22 | 186 |
(b) Reactor validation testing. Systems must use UV reactors that have undergone validation testing to determine the operating conditions under which the reactor delivers the UV dose required in subparagraph (4)(a) of this rule above (i.e., validated operating conditions). These operating conditions must include flow rate, UV intensity as measured by a UV sensor, and UV lamp status.
(c) Reactor monitoring.
Author: Dennis D. Harrison
Statutory Authority: Code of Ala. 1975, §§22-23-33, 22-23-49, 22-22A-5, 22-22A-6.
History: New Rule: Filed December 18, 2007; effective January 22, 2008. Amended: Filed April 21, 2009; effective May 26, 2009.