- (1) The maximum filtration rate shall not exceed the manufacturer’s documented performance. Loading rates will be considered based on manufacturer’s information, pilot testing and actual records from operating treatment units. The Department may consider alternate filtration technologies other than conventional filtration upon submission of a written request accompanied by all necessary product information.
- (2) Reclaimed water filtration facilities must install and operate a filter to waste system that operates each time a filter begins operation. Filter to waste systems shall automatically filter to waste until the effluent meets the required turbidity standard.
Author: Nicholas Caraway
Statutory Authority: Code of Ala. 1975, §§22-22-1 to 22-22-14;
§§22-22A-1 to 22-22A-16 et seq., as amended.
History: New Rule: Filed August 25, 2015; effective September 29, 2015.