OPINION
for the Court.
Thе issue presented in this petition is whether G.L.1956 § 5-6-2 permits only a licensed electrician to install underground hollow polyvinyl chloride (PVC) material that is devoid of any electrical wiring or conductors. The Board of Examiners of Electricians (the board), the Rhode Island Department of Labor and Training (DLT), and the Superior Court all determined that § 5-6-2 required a licensed electrician to perform such work. The petitioners, Reilly Electrical Contractors, Inc. (Releo), Michaеl McSheffrey, Robert Rutledge, John Brewer, and Ray Bombardier,
I
Facts and Travel
Having been selected as a subcontractor for an outdoor lighting project taking place at Rhode Island College, Relco’s employees were installing PVC material beneath a soccer field on October 27, 2005. Although the hollow PVC material did not contain any electrical wiring at that time, the future purpose of the tubing was to house and protect electrical conductors and wiring. On that day, Robert Raim-bault, the chief electrical inspector for the state, observed four men holding the PVC material over their heads as they fed it into the excavated ground. After questioning the men, Mr. Raimbault discovered that only one of the four men had a current Rhode Island electrician’s license.
On March 15, 2006, a hearing was held before the board (the first board hearing).
Mr. Raimbault also acknowledged that the PVC material being handled by the Releo employees “was rated as electrical material!,]” and was “described in the elec
At the close of the first hearing, the board unanimously recommended that the director of DLT deny the appeal, which she did on April 20, 2006. Undeterred by the outcome of their administrative appeal, petitioners filed an appeal of DLT’s decision in the Superior Court under G.L.1956 § 42-35-15.
After the filing of that appeal, however, DLT vacated the contested violations and fines based on due рrocess concerns that the fines should not have been issued prior to a hearing. Thereafter, DLT reissued to Releo and its employees new notices of violation, based on the conduct of October 27, 2005, this time affording them the right to a hearing before any action took place. The petitioners again appealed the reissued notices to the board.
On February 20, 2008, a second hearing was held before the board (the second board hearing). The bulk of the evidence at this hearing was the record from the first board hearing, which the board reviewed. At the second board hearing, Mr. Raimbault confirmed that the PVC material in question was “consistent with the electrical conduit constructed of PVC material exclusively made for the electrical industry as listed and tested[.]” He further clarified that “it [was] electrical pipe constructed of PVC [that] is not the type used for plumbingf.]”
After the second hearing, the board again unanimously recommended that the director of DLT affirm the violations for the events of October 27, 2005, which she did on February 25, 2008. The petitioners filed a timely appeal of this decision with the Superior Court by amending the prior complaint that they had previously filed.
On May 13, 2010, a hearing before a justice of the Superior Court was held on the matter. In their appeal before the hearing justice, petitioners asserted that the board’s decision violated § 42-35-15 because it was arbitrary, capricious, and clearly erroneous. Specifically, petitioners argued that what took place on October 27, 2005, was merely preparatory work involving PVC “pipe” that by itself could not in any way conduct electricity. The petitioners, in their argument before the hearing justice, averred that the word “conduit” was something that in and of itself conducts electricity — such as an insulated wire or cord. Thus, the petitioners explained, because the PVC matеrial handled by the Releo employees could not conduct electricity, it was not conduit at all, but rather “a protection device” used to protect wires — or in their view, conduit — that are subsequently threaded through the pipe.
In a written decision issued on July 20, 2010, the hearing justice denied petitioners’ appeal by ruling that the PVC material was conduit pursuant to § 5-6-2 and therefore an electrician’s license and state permit were required for its installation.
II
Standard of Review
This Court has frequently stated that, when considering an administrative appeal, “the scope of our review, like that of the Superior Court, is an extension of the administrative process.” Auto Body Association of Rhode Island v. State Department of Business Regulation,
On certiorari, we do not weigh the evidence but rather, as an extension of the administrative process, we limit the scope of our review to the record as a whole “to determine whether [any] legally competent evidence exists” in it to support the trial court’s decision. Champlin’s Realty Associates,
Ill
Discussion
We begin our analysis by citing the portion of the Rhode Island statute at issue in this petition. Section 5-6-2, entitled “Work for which license required[,]” provides in pertinent part:
“(a)(1) No person, firm, or corporation shall enter into, engage in, solicit, advertisе, bid for, or work at the business of installing wires, conduits, apparatus, fixtures, electrical signs, lightning protection equipment * * * and other appliances for carrying or using or generating electricity for light * * * or power purposes * * * unless that person, firm, or corporation shall have received a license and a certificate for the business, issued by the state board of examiners of electricians of the division of professional regulation of the department of labor and training in accordance with the provisions set forth in this chapter.”
The single issue in this matter is whether the PVC material Releo and its employees handled was “conduitf ] * * * for carrying * * * electricity” as described in § 5-6-2. If the PVC material was conduit to be used in that manner, as the board and the Superior Court determined, then Releo violated the statute and the citations it received were justified.
Intended Purpose of PVC Material
The petitioners argue that the work performed on October 27, 2005, and observed by Mr. Raimbault, was not electrical in nature, but rather “excavation and other preparatory work.” In support of this argument, petitioners cite testimony elicited at the first board hearing, at which Mr. Raimbault testified that the PVC material was hollow and that he did not see any electrical cords within it. The petitioners suggest that Mr. Raimbault made an unfounded assumption that the PVC material would be later used for an electrical purpose; specifically, the petitiоners assert that “he was merely assuming that electrical conductors would at some later point be installed at [the] site.” (Emphasis in original.)
A review of the record demonstrates to this Court that the PVC material handled on the date of the citations’ issuance was conduit, inherently capable of carrying electricity, in that it would ultimately house and protect electrical conductors. At the first board hearing, a state inspector testified that Releo was “installing] electric conduit for some lighting at the soccer field.” Mr. McSheffrey himself testified that the scope of Relco’s subcontracting work at the soccer field was “[basically just track and field lighting.” Also, on October 26, 2005, a day before the inspection, Releo applied for an electrical permit from the City of Providence that explicitly described the electrical work to be performed.
Moreover, at the first board hearing, Mr. Raimbault testified that the PVC material Releo was installing in the ground was “used to carry electrical conductors.” He further testified that in his profession, the next step after the PVC material is installed in the ground is to install the electric conductors.
2
The Unistrut Corp. Precedent
The petitioners also contend that, as a matter of law, the Superior Court’s decision was clearly erroneous because it contravenes this Court’s holding in Unistrut Corp '. v. State Department of Labor and Training,
In Unistrut Corp., we disagreed with the board and the Superior Court’s interpretation of the statute and held that “the administrative body interpreted the term apparatus out of context and only in its general sense[.]” Unistrut Corp.,
Although there are similarities between Unistrut Corp. and this case, there are also discrete differences, and we are satisfied that the hearing justice was correct in her determination that Unistrut Corp. does not apply to the present matter.
More importantly, unlike Unistrut Corp. — where a clear definition of apparatus was lacking, leading the board and the Superior Court to apply an erroneously broad definition — here, a certain meaning of conduit is readily apparent from the
As the hearing justice noted, the National Electrical Code (NEC)
Moreover, testimony at the first and second board hearings also reaffirms that the PVC material in the present matter was PVC conduit that is specifically manufactured and designed to carry electricity. At the first hearing before the board, both Mr. McSheffrey and Mr. Raimbault described the PVC material as “electrical conduit.” (Emphasis added). Mr. McSheffrey himself conceded that the PVC material handled by his employees was “a UL listed electrical product[.]” Mr. Raimbault also acknowledged that the PVC material was “rated as electrical material, ]” that it was “the standard 10-foot gray lengths of conduit which we know as electrical conduitf,]” and that what he observed the Releo employees performing was “standard electrical installation practice[.]”
As we held in Unistrut Corp., the language of § 5-6-2 is clear and unambiguous. Unistrut Corp.,
A plain reading of § 5-6-2 supports the DLT’s citations imposed upon Releo. The operative word in the statute is “for,” as it signals when a licensed electrician is needed. As it is written, a licensed electrician is required to install any conduit when the purpose of such conduit is “for carrying * * * electricity[.]” Section 5-6-2 (emphasis added). Clearly, the PVC conduit in this case was not to be used for the passage of air or water, but specifically for the carrying of electrical conductors and electricity. Further, we agree with the hearing justice that the petitioners’ argument—that the PVC conduit in question did not fall under § 5-6-2 because no wires or conductors were present within the PVC conduit itself—would reduсe the term conduit in the statute to “mere surplusage.” In re Harrison,
The substantial record developed below establishes convincingly that the PVC material being installed by the petitioners was conduit for the carrying of electricity pursuant to § 5-6-2, and because the meaning of conduit is certain and specific, our holding in Unistrut Corp. does not apply.
IV
Conclusion
“When deciding a case on certiora-ri, our task is ‘to discern whether any legally competent evidence supports the lower tribunal’s decision and whether the decision[-]maker committed any reversible errors of law in the matter under review.’ ” Pierce v. Providence Retirement Board,
Accordingly, the petition for certiorari is denied. The judgment of thе Superior Court is affirmed, and the papers in this case may be remanded to the Superior Court with our decision endorsed on it.
Notes
. Michael McSheffrey, Robert Rutledge, John Brewer, and Ray Bombardier were, at that tíme, employees of Releo.
. In fact, one person was an electrician’s apprentice in Massachusetts, one had an expired apprentice license, and one had no electrical credentials whatsoever.
. Mr. McSheffrеy, besides being a master electrician, was secretary and vice president of operations for Releo.
. General Laws 1956 § 5-6-25 reads:
"All electrical work covered in this chapter, which is done in the state of Rhode Island and/or any city or town having rules and requirements for that work, shall be done in accordance with those rules and requirements. Failure of any licensee to do that work in that manner, or his or her failure or refusal to correct the work with reasonable promрtness after notice by local inspection or enforcement authorities where the notice is required by law, when reported to the division of professional regulation, shall be grounds for suspension or revocation of the license, in the discretion of the division after proper notice and a hearing before and upon the recommendation of the board of examiners of electricians to the director of labor and training.”
.This was the first of twо board hearings conducted for petitioners’ appeal. The second board hearing is discussed infra.
. Later in the hearing, however, petitioners' counsel acknowledged that the PVC material was "conduit,” but not an "electrical conduit.” However, counsel qualified this acknowledgment by arguing that although the PVC material may be considered conduit itself, it does not, by itself, conduct electricity. Rather, the electrical conductors that may be placed within it perform the actual carrying of electricity.
. On Relco’s application for an electrical permit there was a space for the applicant to describe the work to be performed. A handwritten notation in the space provided, presumably written by a Releo employee, reads “[¡Installation of a 250 amp service 277/480 volt * * * from new panel. Installation of 4 circuits[, one] for each pole light.”
. At the Superior Court hearing, petitioners' attorney also acknowledged that electrical conductors would be installed in the PVC materials at some point in the future, and that such installation would require an electrician’s license.
.It is not lost on the Court that Relco’s corporate name itself (Reilly Electrical Contractors, Inc.) further supports our holding that the work for which they were hired to perform was fundamentally electrical in nature.
. To support their position, petitioners also citе an unpublished decision of the Superior Court that vacated DLT citations issued to a subcontractor for installing a lightning protection system, allegedly in violation of an earlier rendition of G.L. 1956 § 5-6-2. Northeast Lightning Protection Systems, Inc. v. State Department of Labor and Training,
. In fact, the word "conduits” immediately precedes apparatus in § 5-6-2, quoted supra.
.In Unistrut Corp., we noted that the Superior Court magistrate, in searching for а definition of apparatus, relied on a Ninth Circuit case that defined the term as “a collection or set of materials * * * [or] * * * appliances * * * designed for a particular use.” Unistrut Corp. v. State Department of Labor and Training,
. As the first standardized U.S. electrical code, the National Electrical Code is now used in all fifty states and all U.S. territories. National Electrical Code Handbook, Preface at ix. (11th ed.2008).
. The board, in an apparent effort to distinguish the PVC conduit at issue from commonplace PVC pipe, made the following inquiry of Mr. Raimbault at the first board hearing:
"[THE BOARD]: The PVC conduit which is listed to carry electric conductors, could you put air into that conduit? Can that conduit be used for air travel?
"MR. RAIMBAULT: No.
*848 ''[THE BOARD]: Can that conduit be used for water?
"MR. RAIMBAULT: No.”