Plaintiff appeals as of right the directed verdict in favor of defendants and the trial court’s limitation of the scope of plaintiffs expert testimony. Defendants cross appeal the trial court’s denial of their motion for summary disposition of plaintiff’s Uniform Commercial Code (ucc), MCL 440.1101 et seq.-, MSA 19.1101 et seq., claim and the denial of their motion to dismiss plaintiff’s claim on the ground that plaintiff failed to preserve all relevant evidence. We affirm the trial court’s limitation of the scope of plaintiff’s expert testimony and its denial of defendants’ motions to dismiss plaintiff’s ucc claim. We reverse the trial court’s grant of a directed verdict in favor of defendants, and we remand for a new trial with regard to plaintiff’s UCC claim.
This is a products liability action brought by plaintiff MASB-SEG Property/Casuaity Pool, Inc., as subrogee of the Calhoun County Area Technology Center, which arose out of a fire that occurred in the “tool crib” of the technology center on December 3, 1993. Plaintiff alleged that the fire was caused by a defective fluorescent light that was manufactured by Metalux, a division of Cooper Industries, Inc., and sold to Medler Electric Company, from whom the technical center bought the fixture.
*396 The tool crib was an area within the construction technology lab where power tools and other equipment were stored under padlock for security purposes. It encompassed approximately two hundred square feet in the middle of the large open room where students completed their construction projects, and it was constructed of studs with wire mesh sides and a door that was latched with a safety lock. The tool crib was equipped with eight-foot-long fluorescent lighting fixtures located at the top of the bay area, and it was not equipped with a sprinkler system. The lights in the crib were installed by electrical program students.
Frederick Kempski, a fire investigator for the Michigan State Police and an expert witness for plaintiff, testified that he was called to investigate the fire at the school. Kempski testified that, from the heat distortion on the electrical metal jig that he found on the floor, he believed it could have been an accidental cause of the fire if it had been energized or plugged in. He also testified that there was more burning high in the crib than lower toward the ground, which is indicative of an accidental fire. He testified that in the northwest area of the crib, virtually everything that could bum was burned to ash. This is consistent with the fact that a fire bums hotter and longer in the area of origin of the fire, so there will be more damage in that area. Kempski ruled out spontaneous combustion as a possible cause. Additionally, in one photograph he identified an electrical conduit that was in the same area at ceiling height, but stated that it did not appear to be the origin or cause of the fire. He testified that the origin of the fire was in the west end of the tool crib at the ceiling level of the crib and just *397 below the floor level of the loft area. He stated that the only thing in the area of the origin of the fire that could have served as an ignition source was the fluorescent light.
Dan Jones, an independent fire investigator who was called to the scene of the fire, testified that he examined the exterior of the building and then entered the building through the front door and began his investigation. He testified that from the smoke staining that had occurred, he determined that the origin of the fire was inside the building. Jones determined that the electrical system was in normal operating condition, and there were no breakers tripped and no indication that there was any problem with the internal disconnects of the electrical system. The heating units and boilers were operating normally, and there was no indication that they were a possible cause of the fire. By working his way from areas with the least fire damage to those with the most, Jones narrowed the area to the tool crib. He further testified that the padlock that secures the door to the tool crib was still in place and locked. He observed several two-by-fours that were part of the structure at the west end of the tool crib and noted that the charring on them indicated that the fire was in the west end. Jones also testified that the magnesium float, of which remains were found in the tool crib, did not cause the fire. He examined the electrical outlets in the west end of the tool crib to determine whether something might have been plugged into the receptacles, and he found that there was no indication that the receptacles might have caused the fire. He also stated that there was no indication of any internal *398 arcing, sparking, or holes on the inside of the receptacles.
Norman Reese testified for plaintiff as an expert in a limited capacity as an electrical engineer. He testified that at Jones’ request he inspected the ballast that was attached to the light fixture that was removed from the tool crib. He testified that the capacitor in the light fixture was melted into a solid block and that it had completely lost its form and was unrecognizable as a capacitor. He stated that there is virtually no way to test the capacitor once it takes on this form, because as soon as the short circuit occurs, the two plates melt together and are completely destroyed. Reese testified that, judging from the bum patterns on the fixture itself from the base of the ballast, the melted form of the capacitor, the position of the capacitor on the ballast, and the tar running beneath the ballast, which indicated that it was heat from above that caused the melted capacitor, it was his opinion that the capacitor had failed.
Before cross-examining Reese, defendants moved for a directed verdict. After hearing testimony from defense experts outside the presence of the jury, the trial court granted the motion.
Plaintiff first argues that the trial court erred in directing a verdict in favor of defendants, because plaintiff presented evidence that a defect existed at the time the product left the manufacturer. We agree. In reviewing a trial court’s decision regarding a motion for a directed verdict, this Court views the evidence presented up to the time of the motion in the light most favorable to the nonmoving party, grants that party every reasonable inference, and resolves any conflict in the evidence in that party’s
*399
favor to decide whether a question of fact existed.
Hatfield v St Mary’s Medical Center,
A plaintiff bringing a products liability action, under either a negligence or a warranty theory, must show that the defendant supplied a product that was defective and that the defect caused the injury.
Mulholland v DEC Int’l Corp,
We find that, viewing the evidence in a light most favorable to the plaintiff, a trier of fact could have concluded that defendants supplied a product that was defective and that the defect caused the plaintiff injury. Plaintiff’s expert, Norman Reese, testified that, on the basis of the bum pattern he examined on the fixture itself and on the base of the ballast, he concluded that the capacitor on the ballast failed. Frederick Kempski testified that the origin of the fire was in the west end of the tool crib, at the ceiling level of the crib and just below the floor level of the loft area. *400 He testified that the only possible ignition source in this area was the fluorescent light. On the basis of this evidence, we find that the trial court erred in directing a verdict in favor of defendants.
Plaintiff next argues that the trial court erred in limiting the scope of plaintiffs experts’ testimony on the ground that plaintiff failed to preserve evidence. Plaintiff relies on the fact that the allegedly defective product, the light fixture, was preserved and available for inspection by defendants and that defendants demonstrated no prejudice as a result of plaintiff’s failure to preserve other evidence from the fire scene. Defendants argue on cross appeal that the trial court abused its discretion in denying their motion to dismiss plaintiff’s claim on the ground that plaintiff failed to preserve all relevant evidence other than the light fixture itself.
A trial court has the authority, derived from its inherent powers, to sanction a party for failing to preserve evidence that it knows or should know is relevant before litigation has commenced.
Brenner v Kolk,
[I]n a case involving the failure of a party to preserve evidence, a trial court properly exercises its discretion when it carefully fashions a sanction that denies the party the fruits of the party’s misconduct, but that does not interfere with the party’s right to produce other relevant evidence. An appropriate sanction may be the exclusion of evidence that unfairly prejudices the other party or an instruction to the jury that it may draw an inference adverse to the culpable party from the absence of the evidence. [Id. at 161 (citations omitted).]
*401 Dismissal of a case is a drastic step. Before imposing such a sanction, the trial court must consider lesser sanctions such as the exclusion of evidence that is unfairly prejudicial to defendants because of plaintiffs failure to preserve the evidence. Id. at 163.
We find that the sanction imposed by the trial court was appropriate under the circumstances of this case. Plaintiffs failure to preserve evidence from the fire scene prejudiced defendants by depriving them of the opportunity to investigate alternative causes for the fire. Therefore, the trial court properly excluded expert testimony regarding evidence that was not preserved.
Hamann v Ridge Tool Co,
Defendants next argue on cross appeal that the trial court erred in denying their motion for summary disposition after concluding that the economic loss doctrine applies in this case. We agree. The economic loss doctrine provides that where a plaintiff seeks to recover for economic loss caused by a defective product purchased for commercial purposes, the exclusive remedy is provided by the ucc.
Neibarger v Universal Cooperatives, Inc,
Here, the purchaser of the light fixture was a commercial entity, an industrial school, and the seller was a retailer for the original manufacturer. Thus, both parties were sophisticated commercial entities who had the knowledge and ability to allocate liability in their purchase and sale agreement. Furthermore, the light fixture was for a commercial purpose, in that it was installed as a student project in the tool crib at the industrial training school and used for the purpose of maintaining the school premises. Therefore, because the consequences of the product’s potential failure were likely to have been within the contemplation of the parties when they entered into the agreement for the sale of the light fixture, the economic loss doctrine applies. Therefore, plaintiff’s exclusive remedy is provided by the UCC, Neibarger, supra at 538, and its products liability claim should have been dismissed.
Plaintiff relies on
Detroit Bd of Ed v Celotex Corp (On Remand),
In the present case, plaintiffs do not allege that defendants’ products were inferior in quality or did not work for their intended purpose. They do not claim any injury to the products themselves. Rather, they claim that defendants’ products are safety hazards that have created a potential health threat and caused them to suffer damages in abating the hazard. We also observe that it is highly unlikely that the parties could have anticipated and bargained over the hazards of asbestos at the time the products were sold, which was apparently years before the risks of the material were known. In short, the risk involved here is not the type that is allocated to a party through negotiation. [Id. at 704-705.]
This Court’s decision in Celotex was not based strictly on the fact that the product was a safety hazard, but rather on the fact that the specific type of danger posed by the product could not have been in the contemplation of the parties at the time they entered into their sales agreement. In contrast, the potential failure of the capacitor within the light fixture in the present case, and the damage caused by the resulting fire, were direct and consequential losses that were within the contemplation of the parties when they entered into the agreement for the sale of the light fixture. Therefore, plaintiff’s only remedy is through the ucc, and the trial court erred in failing to grant *404 summary disposition in favor of defendants with regard to plaintiffs tort claim.
Defendants next argue that the trial court erred in denying their motion for summary disposition of plaintiffs UCC claim because plaintiff was required by MCL 440.2607(3)(a); MSA 19.2607(3)(a) to provide reasonable notice of the asserted breach of warranties and failed to do so. We disagree.
Defendants argue that plaintiff determined by early January 1995 that the capacitor of the light fixture had failed, but did not notify defendants until May. Plaintiff claims that it did not determine that defendant Metalux was the manufacturer of the product until April and that it notified defendants within a few weeks. It appears to this Court that plaintiff acted in good faith and notified defendants of the alleged breach of warranties within a reasonable time after discovering the identity of the manufacturer of the light fixture. Therefore, plaintiffs UCC claim is not barred.
Affirmed in part, reversed in part, and remanded for a new trial with regard to plaintiffs claim of breach of warranties under the UCC. No taxable costs pursuant to MCR 7.219, neither party having prevailed in full. We do not retain jurisdiction.