86 W. Va. 628 | W. Va. | 1920
The judgment for $3,500.00 under review on this writ of error was recovered in an action for damages for a personal injury, alleged to have been caused by the negligence.of the defendant, a corporation supplying natural gas for light and fuel, in respect of its gas mains, pipes and meter. A wife sues for the injury, her husband joining her in the action. The specific assignments of error challenge the sufficiency of the evidence to sustain the' verdict and the correctness of a certain instruction given at the ' instance of the plaintiffs.
In the second count of the declaration and the evidence, the charge of negligence is limited to alleged defectiveness of the meter connections and conduct of the defendant respecting the same. The theory of the plaintiffs is that, by reason of the sliding of the ground over which the meter stood and an accumulation of ice on the meter, a connection between it and the servicé pipe, called in some places a union and in others a brass or bronze nipple, brolle and permitted an escape of gas which found its' way into the building in which the plantiffs resided, and, being accidentally ignited by a match struck by the female plaintiff, caused an explosion in which she was knocked down and severely' burned, notably about the head, arms and chest. The house, a one-story, three-room, frame structure, had a kitchen and cellar1 under a portion of it, made by an excavation in a hillside and enclosed by a hollow tile wall which, conforming to the horizontal dimensions of the house, constituted its foundation. The explosion occurred in the cellar and-kitchen and the gas or other explosive substance seems to have been in the former. At about 5:30 A. M. February 9,1918, something like a half an hour after the husband had come down into'the kitchen and refreshed the' coal fire with a bucket of coal procured from the cellar and lit a lamp, and almost immediately after the wife came down, the latter opened the cellar door and struck a match on or about it, intending to enter the cellar for some meat, and the explosion occurred. She was rendered unconscious, her clothing set on fire
In this work of restoration, evidence of the cause of the explosion, relied upon by both plaintiffs and defendant, was discovered; a broken connection in the cellar made one of the principal grounds of the defense. and a broken connection at the! meter, relied upon by the plaintiffs, in connection with. other facts, as proof of negligence on the part of the defendant. ,If the break in the cellar occurred before the explosion, the gas causing the injury no doubt accumulated there in consequence, and, as the defendant was not responsible for the safety or main-1 tenance of that pipe, it admittedly would not be liable under the' circumstances. On the other hand, as it owned, controlled and had placed the meter, there may be liability if the accumulated gas came from the bréale found in the meter connection. Thd meter was disturbed by the explosion and it is insisted that the break in that connection was a result, not a cause, of the accident.
Claiming that, if either break antedated and caused it, the probabilities as to which of them did so are equal, the defendant invokes the well settled legal proposition that, in such a case, a verdict against the defendant cannot be permitted to stand, because the plaintiff, carrying the burden of proof and being bound to make out a case of negligence afflrmatively, has not succeeded in doing so. Moore v. Heat & Light Co., 65 W. Va. 552; Jacobs v. Baltimore & Ohio R. Co., 68 W. Va. 618.
There is evidence in the case, however, giving the theory of the plaintiffs an emphasis not possessed by that of the defendant and tending to disprove the latter. The connection in the cellar had efficiently and safely performed its function for more' than two years and there is no evidence tending to prove disturbance of it at anytime prior to the explosion. It was a bushing used near the cellar door in reducing the inch pipe which entered the cellar from the meter, passing through the weatherboarding over the hollow tile wall and going up the wall inside and then along the'
If,- however, the broken connection at the meter, permitting escape of about 50 cubic feet of gas per hour, antedated the explosion, liability is denied on the ground of lack of proof that the escaping gas entered the cellar, and the tendency of expert testimony adduced, to prove that it did not. The meter stood but a few inches from the tile wall and not far below the top thereof and the bottom of the frame structure. In the tile wall there was a small window and there is evidence tending to prove openings around the window and also a crack or open space between the weatherboarding and the top of the wall, all of sufficient size to admit considerable air and gas, if the latter was escaping and for any reason seeking entrance. In our opinion, it is immaterial whether the night was windy or whether the wind, if any, blew toward or fromi the northeast. Cold and dense air seeks warm and rarified areas, and readily finds its way through small apertures. The air in the cellar was no doubt warmer than that outside. At any rate, there was a coal fire in the kitchen warming the air in that room, to which air could drift from the cellar through spaces around the door and thus tend to the creation of currents from the outside into the cellar. The entrance of only a small quantity of gas into the cellar was sufficient to cause the explosion. Less than 100 cubic feet of gas combined with all the air in the cellar would have rendered it explosive. But there need not have been so large a quantity as that, for such as entered naturally went to the top and may have formed a small explosive pocket there. The expert testimony denies that the wind blew it in, but it. may have drifted in without the aid of the wind and in spite of its disturbing tendency. Upon their common knowledge of the natural laws and tendencies of gas and air, the jury were warranted in finding that escaping gas could have entered the ■cellar from the broken outside fixture.
As the meter and its connections were furnished, installed and maintained by the defendant, and the plaintiffs had no right to molest or interfere with it, we are of the opinion that the duties of proper installation, maintenance, and inspection of it and the selection of safe and suitable fittings for connection thereof with the service pipes rested upon the defendant. Under the contract, it was the property of the defendant and molestation thereof by the, consumer was forbidden.
But an insuperable obstacle to recovery, upon the evidence adduced, is found in the fact that the alleged cause of the fracture, of the fitting was the dislocation of the service pipe which, the plaintiffs were bound to maintain. No duty of maintenance thereof rested upon the defendant. This is impliedly, if not expressly, held in Cornfield v. W. Va. Central Gas Co., 80 W. Va. 731, and specifically he,ld in Smith v. Pawtucket Gas Co.. 24 R. I. 292; and King v. Consolidated Gas Co., 90 App. Div. N. Y. 166. Upon principles declared in the cases just cited and others referred to in the note to Consolidated Gas Co. v. Connor, 32 L. R. A. (N. S.) 809, there might be liability upon the defendant, if a leak had been discovered and brought to its attention, upon the theory of duty either to make the pipe or fixture safe or cut off the, gas; hut, in this case, no leak had been discovered. There was only a displacement or disturbance of the service pipe, known to the plaintiffs and not caused by any act or omission of the defendant. That dislocation caused by the slipping ground on the premises of the plaintiffs disturbed the meter and finally broke the fitting. There is no evidence that the fitting was unsuitable or inappropriate or that the, mere weight of the meter broke it. Some witnesses say it was less dependable than similar fittings made of other.materials, hut it was a standard fitting commonly used. Of course there was no duty resting upon the plaintiffs to prevent the sliding of the land, but they were under duty to keep their own service pipe in place and to prevent it from breaking the defendant’s fitting by its dislocation.
It is .argued that the plaintiffs are barred from recovery -by reason of an accumulation of ice on the meter, which, they claim, may have caused the fracture, because- it too was preventable. The, jury could have found, however, that, as the large icicle rested on the ground and enveloped the meter, it practically supported its own weight and, therefore, did not cause the, fracture.
Instruction Ho. 1, given at the instance of the plaintiff is not aptly drawn. In general terms it placed upon the defendant duty to maintain its pipe lines and prevent injurious escape •of gas, and advised the jury that, if they should believe a quantity of gas escaped from the pipe lines used by the defendant in transporting and supplying gas, because of its negligence, and injured the plaintiffs, there, was liability, unless it should be further found that the plaintiffs had been guilty of contributory negligence in the premises. It should have limited the duty of the defendant- to the meter and its fittings. The defect might not be cause for reversal, but it should be remedied for the purposes of the new trial, if one should occur.
The judgment complained of will be reversed, the verdict set aside, as being contrary to the law and the evidence, and the case remanded for a new trial.
Reversed and remanded.